Product Catalog

General description.

Cable manufactured with copper, all aluminum conductor (AAC) or aluminum conductor steel reinforced (ACSR) with extruded semi-conductor shield over the conductor and black cross-linked polyethylene (XLPE) insulation jacket.

Specifications.

Viakon's covered cables meet the following specifications:

  • CFE E0000-29 Covered cables for overhead lines from 15 to 38 kV.
  • LFC GDD-035 Covered Cables 23.

Note: The LFC specification covers only some sizes for 25 kV, for more information, contact our Engineering Department.

Main applications:

  • Covered cables are suitable for use in medium voltage overhead electrical energy distribution systems in wooded areas.

Characteristics.

  • Maximum operation voltage: 15000, 25000, and 35000 V.
  • Maximum operation temperature in the conductor: 90°C
  • Copper conductors are made with hard drawn copper.
  • Aluminum conductors are manufactured with 1350 - H19 alloy hard drawn aluminum.
  • ACSR conductors are manufactured with 1350 - H19 alloy hard drawn aluminum and a steel core.
  • Black covering which makes them sunlight resistant.
  • Because theses cables do not have an insulation shield they are considered to be non-insulated cables, and therefore they must be subject to the care and precaution of non-insulated cables.

Advantages.

  • Cross-linked polyethylene insulation jacket makes them resistant to abrasion caused by tree branches.
  • Sunlight resistant.
 
Product Catalog  

Printing version

VIAKON'S COVERED CABLES 15 kV
Item NumberSizeTransversal Section Nominal AreaNumber ofwiresInsulation Nominal ThicknessApproximated Overall DiameterApproximated Total WeightCurrent Carrying Capacity*
CFEAWG/kcmilmm2 mmmmkg/100 mAmpere
COPPER CONDUCTOR
DM271/053,4872,515,761260
DM283/085,0173,019,396345
ALUMINUM CONDUCTOR (AAC)
Q2811/053,4872,515,726200
Q0343/085,0173,019,340270
Y815266,8135,2193,022,758345
DM29336,4170,5193,024,670395
ACSR CONDUCTOR
W9171/053,486 / 12,516,334195
Q2823/085,016 / 13,020,152260
DM30266,8135,226 / 73,023,177345
Q040336,4170,526 / 73,025,194395

VIAKON'S COVERED CABLE 25 kV

Item NumberSizeTransversal Section Nominal AreaNumber ofWiresInsulation Nominal ThicknessApproximated Overall DiameterApproximated Total WeightCurrent Carrying Capacity*
CFEAWG/kcmilmm2 mmmmkg/100 mAmpere
COPPER CONDUCTOR
DM311/053,4874,018,869260
DM323/085,0174,021,3102345
ALUMINUM CONDUCTOR (AAC)
DM331/053,4874,018,834200
DM343/085,0174,021,346270
Q032266,8135,2194,024,865345
F961*336,4170,5194,026,778395
ACSR CONDUCTOR
Y956*1/053,486 / 14,019,442195
DM353/085,016 / 14,022,258260
DM36266,8135,226 / 74,025,284345
Q035336,4170,526 / 74,027,2101395

* NOTE: To get the Item Number of sizes specified by LFC contact our Engineering Department.

VIAKON'S SEMI-INSULATED CABLE 35 kV
Item NumberSizeTransversal Section Nominal AreaNumber ofwiresInsulation Nominal ThicknessApproximated Overall DiameterApproximated Total WeightCurrent Carrying Capacity*
CFEAWG/kcmilmm2 mmMmkg/100 mAmpere
COPPER CONDUCTOR
DM371/053,4875,321,576260
DM383/085,0175,324,0110345
ALUMINUM CONDUCTOR (AAC)
DM391/053,4875,321,541200
Z4483/085,0175,324,054270
DM40266,8135,2195,327,575345
DM41336,4170,5195,329,489395
ACSR CONDUCTOR
BS161/053,486 / 15,322,149195
BS153/085,016 / 15,324,867260
DM42266,8135,226 / 75,327,994345
BS14336,4170,526 / 75,329,8112395

* Based on Table 310-69 and 310-70 of the NOM-001-SEDE Standard for an operation temperature of 90°C and at a room temperature of 40°C.
Notes: Dimensions and weights are subject to manufacturing tolerances.

DISTRIBUTION 05